Lynx Smart BMS If the dip switches have been accidentally programmed incorrectly or need to be reprogrammed to a different address after commissioning the Lynx Smart BMS, you must restart the BMS (OFF mode and back to Standby or ON mode). This action is necessary to correctly adopt the Lynx Distributor status in VictronConnect and the GX device. Restarting the BMS will also reset the error message "W-D02: Communication with Distributor [A, B, C, or D] lost" in VictronConnect and clear the Lynx Smart BMS alarm "Distributor [A, B, C, or D] connection lost." Use the VictronConnect app to give each fuse a custom name (maximum 16 characters).
If the fuse name is empty (0 characters), the fuse will be disabled and ignored for monitoring. 1. Navigate to the Settings page by clicking the cog wheel icon at the top right hand corner. 2. On the Settings page scroll down to the Lynx Distributor settings. 3. Tap on a distributor name. A new menu opens with all 4 fuses. 4. Tap on a fuse to assign a custom name and/or to disable the fuse manually from monitoring. Page 20 Configuration and settings