Manual - BMV-700H 7.6.5. Shunt current When a shunt other than the one supplied with the battery monitor is used, use this setting to set the rated current of the shunt. 7.6.6. Shunt voltage When a shunt other than the one supplied with the battery monitor is used, use this setting to change the rated voltage of the shunt. 7.6.7. Battery starts synchronised Note that if the battery monitor settings are accessed via the head unit, this setting will be part of the miscellaneous setting, and if accessed via VictronConnect it will be part of the battery settings. For full information about this setting see the Battery SOC on reset [25] chapter. 7.6.8.
Current measurement direction The current-measurement direction setting allows you to choose on which side of the shunt the battery (or battery bank) is connected. This ensures that current-flow calculations use the correct polarity. Normal mode (off): the battery negative is connected to the shunt’s battery terminal. Reversed mode (on): the battery negative is connected to the shunt’s load terminal. This setting is protected by the "Settings Lock" feature (so if the settings are locked, this setting cannot be changed). This setting was introduced in firmware version v4.19 and is not supported in earlier versions. 7.7.
Additional settings These VictronConnect settings are not located in the VictronConnect settings menu but are located elsewhere in the VictronConnect app. 7.7.1. Reset history This setting can be found at the bottom of the history tab. This setting can also be made via the head unit. For more information see the Clear history [31] chapter. Please be aware that history data is an important tool to keep track of battery performance and is also needed to diagnose possible battery problems. Do not clear the history unless the battery bank is replaced. 7.7.2. Reset PIN code Note that the PIN code is only applicable when connecting to the battery monitor via Bluetooth.
This setting can be found in the settings of the VictronConnect app itself. Leave the battery monitor by clicking on the ← arrow. This will bring you back to the device list of the VictronConnect app. Now, click on the menu symbol next to the battery monitor listing. Page 32 All features and settings Setting Default Range Step size Shunt current (setting 65) 500A 1 - 9999A 1A Setting Default Range Step size Shunt voltage (setting 66) 50mV 1 - 75mV 1mV Setting Default Modes Start synchronized (setting 70) ON ON/OFF VictronConnect app setting Default setting Modes Current measurement direction Normal Normal Reversed