Manual - BMV-700H 9.3.7. State of charge always shows 100% One reason could be that the negative cables going in and out of the battery monitor have been wired the wrong way around, see Charge and discharge current are inverted [36] . 9.3.8. State of charge does not increase fast enough or too fast when charging This can happen when the battery monitor thinks the battery is bigger or smaller than in reality. Check if the battery capacity [13] has been set correctly. 9.3.9. Incorrect battery voltage reading Check if there is an issue with the BATTERY + cable. Perhaps the fuse, the cable itself or one of the terminals is faulty or there is a loose connection. Check for incorrect wiring:

the BATTERY + cable has to be connected to the positive of the battery bank, not midway of the battery bank. 9.3.10. Synchronisation issues If the battery monitor does not synchronise automatically, one possibility could be that the battery never reaches a fully charged state. Fully charge the battery and see if the state of charge eventually indicates 100%. Another possibility is that the charged voltage setting [24] should be lowered and/or the tail current setting [24] should be increased. It is also possible that the battery monitor synchronises too early. This can happen in solar systems or in systems that have fluctuating charge currents.

If this is the case change the following settings: Increase the “ charged voltage [24] " to slightly below the absorption charge voltage. For example: 14.2V in case of 14.4V absorption voltage (for a 12V battery). Increase the “ charged detection time [24] ” and/or decrease the " tail current [24] " to prevent an early reset due to passing clouds. Page 39 Troubleshooting