Victron BMV-712 Smart — 4.7. Configure for use as DC meter

Manual - BMV-712 Smart In VictronConnect see: Settings > Battery > Charge efficiency factor . Via the head unit, see: Setup menu > Setting 06 - Charge efficiency factor . The charge efficiency of lithium batteries is much higher than that of lead-acid batteries. We recommend setting the charge efficiency at 98%. Discharge floor In VictronConnect see: Settings > Battery > Discharge floor . Via the head unit, see: Setup menu > Setting 16 - SoC relay . This setting is used in “the time to go” calculation and is set at 50% by default for lead-acid batteries. However, lithium batteries usually can be discharged significantly deeper than 50%.

The discharge floor can be set to a value between 10 and 20%, unless the battery supplier advises otherwise. Important warning Lithium batteries are expensive and can be irreparably damaged due to very deep discharge or overcharge. Damage due to deep discharge can occur if small loads slowly discharge the battery when the system is not in use. Some examples of these loads are alarm systems, standby currents of DC loads and back current drain of battery chargers or charge regulators. A residual discharge current is especially dangerous if the system has been discharged all the way until a low cell voltage shutdown has occurred. At this moment the state of charge can be as low as 1%.

The lithium battery will get damaged if any remaining current is drawn from the battery. This damage can be irreversible. A residual current of 1mA for example can damage a 100Ah battery if the battery has been left in a discharged state for more than 40 days (1mA x 24h x 40 days = 0.96Ah). The battery monitor draws system with Li-ion batteries is left unattended during a period long enough for the battery monitor power consumption to completely discharge the battery. In case of any doubt about the possible residual current draw, isolate the battery by opening the battery switch, by pulling the battery fuse(s) or by disconnecting the battery positive when the system is not in use. 4.7.

Configure for use as DC meter In the VictronConnect battery monitor settings, go to the "Misc" settings and select "DC energy meter" from the Monitor mode drop-down menu. Once selected, you can choose what application the DC energy meter is used in. Alternatively, navigate to setting 72 on the head unit. For additional information also see the Monitor Mode [41] chapter. Page 17 Configuration