VLT ® 2000 Series I Description of parameters I 002 Setup copy (MENU SET COPY) Value: ✭ No copy (DO NOT COPY) [0] Copy setup 1 to 2 (COPY 1 TO 2) [6] Copy setup 2 to 1 (COPY 2 TO 1) [7] Copy from fact.setting to 1 (FACTORY TO 1) [8] Copy from fact.setting to 2 (FACTORY TO 2) [9] Description of parameters I 000 Language select (LANGUAGE) Value: ✭ English (ENGLISH) [0] German (DEUTSCH) [1] French (FRANCAIS) [2] Danish (DANSK) [3] Function: You can copy Setup 1 to Setup 2 and vice versa. You can always copy the factory setting back to Setup 1 or Setup 2 . Function: The choice in this parameter defines the language to be shown in the display. Description:

You can choose between English, German, French and Danish. Description: Copying starts when you have recorded the required data value and have stored it by pressing the “Menu” key. The software will always return to No copy when copying has been accomplished. Copying takes about 45 seconds. Time out does not activate the copying function. Section 1 Section 2 Section 3 I 001 Menu setup select (MENU SETUP) Value: ✭ Setup (SETUP 1) [1] Setup (SETUP 2) [2] Multi setup (MULTI SETUP) [5] I 003 Operation site (LOCAL /REMOTE) Value: ✭ Remote (REMOTE) [0] Local with external stop (LOC/EXT.STOP) [1] Local (LOCAL) [2] Local and remote (LOCAL+REMOTE) [3] Setup Terminal 29 1 0 2 1 Function:

You can select a menu setup which is different from the factory setting and store it in Setup 1 or Setup 2 . Function: You can choose four different operation sites: Remote, Local with external stop , Local and Local and remote. Description: You start by selecting the setup you want to make or alter. You can choose between Setup 1 or Setup 2 . Then you can alter any data value you like. Your alterations make a setup different from the factory setting. If you choose Multi-setup you can switch between the two setups via terminal 29. The parameters which can be chosen for the two setups have been specially selected. See page 102. For how to change to factory setting see page 48. Description:

If you choose Remote , you can control the frequency converter via the control terminals. However, you can still use the stop key of the control panel (provided you have not chosen to disable this function in para- meter 007). If you choose Local with external stop you must dis- connect the connection between terminals 12 and 27 to activate stop. Local with external stop can only be chosen if Motor coasting, Quick stop, Reset and mo- tor coasting or stop have been chosen in parameter 404 (terminal 27). Choose Local if you want to operate the unit via the keyboard (must be activated in parameter 007). Local and remote adds local and external reference.

This function is selected for access to local reference even when the unit is operated remotely. ✭ = Factory setting. Text in ( ) = Display text. The figures in [ ] are used in bus communication. MG.20.B6.02 – VLT is a registered Danfoss trademark 61