VLT ® 2000 Series I 200 Frequency range (FREQ RANGE) Value: ✭ 0 - 120 Hz [0] 0 - 500 Hz [1] I 202 Max. frequency (MAX FREQUENCY) Value: 0.0-value in para. 200 ✭ 50 H Z Description of parameters Function: Using this parameter you can record a highest frequency limit corresponding to the motor’s maximum speed. Function: Using this parameter you can set and thus limit the output frequency range of the VLT frequency converter. Description: In most cases you can use 0-120 Hz. Description: You can choose a value from f MIN to the value selected in parameter 200 for f MAX ( 120 Hz or 500 Hz). Warning: Only choose 0-500 Hz if you use special motors designed for high speeds.
When the PI controller is active the maximum frequency can be exceeded by 10%. The same applies when slip compensation is active. I 201 Min. frequency (MIN FREQUENCY) Value: 0.0 - f MAX ✭ 0 Section 1 Section 2 Section 3 I 203 Jog frequency (JOG FREQUENCY) Value: 0.0-f MAX ✭ 10 Hz Function: Using this parameter you can record a lowest frequency limit corresponding to the required mini- mum motor speed. The minimum frequency can never be higher than the maximum frequency. Function: This is the fixed output frequency you can select when the “Jog” key is active. See also the description of parameter 511. Description:
You can choose a value from 0.0 Hz to the value selected in parameter 202 for max. frequency. Description: The jog frequency can be lower than f MIN (para. 201) but the highest output frequency is limited by f MAX (para. 202) ✭ = Factory setting. Text in ( ) = Display text. The figures in [ ] are used in bus communication. MG.20.B6.02 – VLT is a registered Danfoss trademark 67