2014-07-02 5011692604-CPD4

Page 1

ENGLISH Thank you for choosing Delta CMC-PD01 network communication card. CMC-PD01 is a PROFIBUS DP network communication card for connecting Delta C2000 series, CH2000 series, CP2000, series, CT2000 series, and AFE2000 series AC motor drives to PROFIBUS DP network. No external power supply is required for CMC-PD01. The power will be supplied from the AC motor drive. EN CMC-PD01 is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration.

To prevent non-maintenance staff from operating CMC-PD01, or to prevent an accident from damaging CMC-PD01, the control cabinet in which CMC-PD01 is installed should be equipped with a safeguard. For example, the control cabinet in which CMC-PD01 is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before CMC-PD01 is powered up. After CMC-PD01 is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on CMC-PD01 is correctly grounded in order to prevent electromagnetic interference. FR CMC-PD01 est un module OUVERT.

Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques. La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil CMC-PD01 pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du CMC-PD01. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante.

Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Functions 1. Supports PZD control data exchange. 2. Supports PKW polling AC motor drive parameters. 3. Supports user diagnosis function. 4. Auto-detects baud rates; supports Max. 12M bps. Product Profile [Figure 1] 1. NET indicator 5. PROFIBUS DP connection port 2. POWER indicator 6. Screw fixing hole 4. AC motor drive connection port 3. Positioning hole 7. Fool-proof groove - 1 -

Page 2

Specifications PROFIBUS DP Connector Communication Electrical Specification Environment Installation Note: The contents below are about installing CMC-PD01 on C2000. PROFIBUS DP Connector 5 9 1 6 Connecting CMC-PD01 to C2000 1. Switch off the power of C2000. 2. Open the front cover of C2000. 3. Place the insulation spacer into the positioning pin at Slot 1 (shown in Figure 2), and aim the two holes on the PCB at the positioning pin. Press the pin to clip the holes - 2 - I nterface DB9 connector T ransmission method High-speed RS-485 T ransmission cable Shielded twisted pair cable E lectrical isolation 500 VDC M essage type Cyclic data exchange C omm.

Card name CMC-PD01 G SD document DELA08DB.GSD C ompany ID 08DB (HEX) S s ( erial transmission 9.6k, 19.2k, 93.75k, 187.5k, 500k, 1.5M, 3M, 6M, 12M bps (bits per second) peed supported auto-detection) P ower supply voltage 5 VDC (supplied by AC motor drive) I nsulation voltage 500 VDC P ower consumption 1 W Weight 28g Noise immunity ESD (IEC 61800-5-1,IEC 6100-4-2) EFT (IEC 61800-5-1,IEC 6100-4-4) Surge Test (IEC 61800-5-1,IEC 6100-4-5) Conducted Susceptibility Test (IEC 61800-5-1,IEC 6100-4-6) Operation/storage Operation: -10 to 50ºC (temperature), 90% (humidity), pollution degree 2 Storage: -25 to 70ºC (temperature), 95% (humidity, non-condensing) S r hock/vibration International standards:

IEC61131-2, IEC68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27 (TEST Ea) esistance PIN PIN name Definition 1 - Not defined 2 - Not defined 3 Rxd/Txd-P Sending/receiving data P(B) 4 - Not defined 5 DGND Data reference ground 6 VP Power voltage – positive 7 - Not defined 8 Rxd/Txd-N Sending/receiving data N(A) 9 - Not defined

Page 3

with the PCB (see Figure 3). 4. Screw up at torque 6 ~8 kg-cm (5.21 ~6.94 in-lbs) after the PCB is clipped with the holes (see Figure 4). Slot 3 Slot 1 Slot 2 [Figure 3] [Figure 2] Connecting to PROFIBUS DP Connector [Figure 4] Insert the connector to the connection port on CMC-PD01 (see Figure 5), and screw up the screws on the connector to ensure tight connection between CMC-PD01 and the PROFIBUS DP connector. [Figure 5] Communication Parameters for C2000 Connected to PROFIBUS DP When C2000 is connected to PROFIBUS DP, please set up the communication parameters for it according to the table below.

The PROFIBUS DP master is only able to read/write the frequency word and control word of C2000 after the communication parameters are set. Note: The value of P09-70 is the address of C2000 in PROFIBUS DP network. The address has to be consistent with the address of C2000 during configuration. Changing the value is P09-70 - 3 - Parameter Functio n Set value Explanation P00-20 Setting up sourc frequency comm e of 8 and The frequency command is controlled by the communication card. P00-21 Setting up sourc operation comm e of 5 and The operation command is controlled by the communication card. P09-30 Decoding metho communication d for 0/1 0:

The old decoding method for the Delta AC motor drive (20XX). 1: The new decoding method for the Delta AC motor drive (60XX). P09-70 Address of com card munication User defined Address of C2000 on PROFIBUS DP network.