2014-07-02 5011699802-FL02
ENGLISH Thank you for choosing Delta’s DVP series PLC. DVPPF02-SL is a PROFIBUS DP slave communication module, used for connecting DVP-SV and DVP-SX2 series PLC to the PROFIBUS DP network. DVPPF02-SL is a left-side extension module, and no external power supply is required when using it. The power is supplied by the PLC MPU (main processing unit). EN DVPPF02-SL is an OPEN-TYPE device. It should be installed in a control cabinet free of airborne dust, humidity, electric shock and vibration. To prevent non-maintenance staff from operating DVPPF02-SL, or to prevent an accident from damaging DVPPF02-SL, the control cabinet in which DVPPF02-SL is installed should be equipped with a safeguard.
For example, the control cabinet in which DVPPF02-SL is installed can be unlocked with a special tool or key. EN DO NOT connect AC power to any of I/O terminals, otherwise serious damage may occur. Please check all wiring again before DVPPF02-SL is powered up. After DVPPF02-SL is disconnected, Do NOT touch any terminals in a minute. Make sure that the ground terminal on DVPPF02-SL is correctly grounded in order to prevent electromagnetic interference. FR DVPPF02-SL est un module OUVERT. Il doit ktre installй que dans une enceinte protectrice (boitier, armoire, etc.) saine, dйpourvue de poussiиre, d’humiditй, de vibrations et hors d’atteinte des chocs йlectriques.
La protection doit йviter que les personnes non habilitйes а la maintenance puissent accйder а l’appareil (par exemple, une clй ou un outil doivent ktre nйcessaire pour ouvrir a protection). FR Ne pas appliquer la tension secteur sur les bornes d’entrйes/Sorties, ou l’appareil DVPPF02-SL pourra ktre endommagй. Merci de vйrifier encore une fois le cвblage avant la mise sous tension du DVPPF02-SL. Lors de la dйconnection de l’appareil, ne pas toucher les connecteurs dans la minute suivante. Vйrifier que la terre est bien reliйe au connecteur de terre afin d’йviter toute interfйrence йlectromagnйtique. Features 1. Supports the loop data transmission between PROFIBUS DP master and many slaves.
2. Auto-detects baudrate; supports max. 12M bps. 3. Self-diagnosis 4. A PLC MPU is extendable to max. 8 DVPPF02-SL modules on its left hand side. 5. Supports max. 100 words of I/O output and 100 words of I/O input. Product Profile & Dimensions 8 1 2 3 4 3 90 DVPPF02 5 9 10 12 13 11 60 Unit: mm [Figure 1] 1. Interface for left-side I/O module 8. Digital display 2. I/O module fastening clip 9. Address switch 3. I/O module positioning hole 10. Positioning clip - 1 - x16 x16 6 7 33
4. POWER indicator 11. Nameplate 5. NET indicator 12. I/O module interface 6. PROFIBUS DP connection port 13. DIN rail mounting slot (35mm) Electrical Specifications 7. Mounting slot clip PROFIBUS DP Connection Port Communication Electrical Specification Environment Components The address switches on DVPPF02-SL are used for setting up the node address of DVPPF02-SL on the PROFIBUS DP network. The switches are two rotary switches x16 0 and x16 1 . Range for each switch: 0 ~ F. See the table below for the setup range for the switches:
Address Switch 1 x16 0 x16 - 2 - Interface DB9 connector Transmission method High-speed RS-485 Transmission cable Shielded twisted pair cable Electrical isolation 500 VDC Data type Cyclic data exchange Module name DVPPF02-SL GSD document DELA0AFE.GSD Product ID 0AFE Serial transmission 9.6k, 19.2k, 93.75k, 187.5k, 500k, 1.5M, 3M, 6M, 12M bps (bits/second) speed supported (auto-detection) Power supply voltage 24 VDC Insulation voltage 500 VDC Power consumption 2 W Weight 115 g RS (IEC 61131-2, IEC 61000-4-3): 80 to 1,000 MHz, 1.4 to 2 GHz, 10 V/m EFT (IEC 61131-2, IEC 61000-4-4): Analog & Communication I/O: 1 kV ESD (IEC 61131-2, IEC 61000-4-2):
8 kV Air Discharge Interference immunity Storage: -25 to 70°C (temperature), 5 to 95% (humidity) Operation: 0 to 55°C (temperature), 5 to 95% (humidity) Storage/operation Shock/vibration International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27 (TEST Ea) immunity Address Definition H’1 ~ H’7D Valid PROFIBUS address H’0 or H’7E ~ H’FF Invalid PROFIBUS address
Example: If you are to set the node address of DVPPF02-SL to 26 (decimal), simply switch x16 1 to 1 and x16 0 to A. 26 (decimal) = 1A (hex) = 1Ч16 1 АЧ16 0 . Notes: Set up the address of DVPPF02-SL when the power is off. Re-power the module after you finish setting up the address. Changing the setting of address when DVPPF02-SL is operating is regarded invalid. Use slotted screwdriver carefully to adjust the address in case you scrape the module. PINs on PROFIBUS DP Connection Port 5 9 1 6 Installation Connecting DVPPF02-SL to PLC MPU 1. Open the fastening ports for the I/O module on the left hand side of the PLC MPU and insert the DVPPF02-SL alongside the fastening clips, as . 2.
Press the clips to make sure the connection is tight, as . DV P28SV 2 1 RUN STOP Connecting to PROFIBUS DP Connection Port 2 [Figure 2] Insert the PROFIBUS DP bus connector into the PROFIBUS DP connection port on DVPPF02-SL. Screw it tight to ensure DVPPF02-SL and the PROFIBUS DP bus are properly connected. - 3 - PIN Name Definition 1, 2 - Not defined 3 Rxd/Txd-P Sending/receiving data P(B) 4 - Not defined 5 DGND Data reference potential 6 VP Power voltage - positive 7 - Not defined 8 Rxd/Txd-N Sending/receiving data N(A) 9 - Not defined