Department of Defense MIL-STD-705C — MIL-STD-705C Generator Sets Engine-Driven Test Methods Standard PDF

Downloaded from https://www.everyspec.com MIL-STD-705C j. To the value obtained in step i above, add the peak value from t = 0 to t = 1. In the example, this time is 0.2 peak. Therefore: 1.2 + 0.2 = 1.4. Multiply the peak value obtained in step j above by the time internal between peaks, which is “1.0“ divided by twice the freqency. In the example, the frequencyis60 Hz. The short-circuit time constant for k. armature winding in the example is 1.4 x 1 = 0.01167 seconds. 120 l. Repeat steps b thru k above for each oscillogram taken during step a above. The short-circuit time constant for armature winding shall be taken as the average of the several values. 432.1.4 Results.

Compare the short-circuit time constant of armature winding with the procurement document requirements. 432.1.5 Procurement document requirements. The following items must be specified in the individual procurement document: a. The maximum allowable short-circuit time constantfor armature winding, if applicable. The voltage connection(s) and frequency(ies) at which this method is to be performed. b. Method 432.1b 2