Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 508.1d PHASE BALANCE TEST (VOLTAGE) 508.1.1 General. Polyphase electrical equipment may not operate properly or may be damaged if the phase voltages of a polyphase generator differ greatly from each other. Also, large different between the phase voltages of a polyphase generator may be an indication that the generator set has been improperly manufactured or damaged. 508.1.2 Apparatus. A frequency meter (or tachometer) as described and illustrated in MIL-HDBK-705, method 104.1 (or 109.2) and a rms indicating ac voltmeter having an accuracy of ±0.1 parent of the reading (or better) shall be require to perform both procedures.
If load is required in procedure I, instrumentation for measuring load conditions shall be as described and illustrated in MIL-HDBK-705. A means of separately exciting the generator will be required if 508.1.3.2, procedure II, is performed. 508.1.3 Procedure. 508.1.3.1 Procedure I. (Generator with Exciter and Voltage Regulator) 508.1.3.1.1 Preparation for test. a. Connect the generator set for one of the voltage connections and frequencies specified in the procurement document. b. Connect the frequency meter to the generator output. c. The same voltmeter shall be used to measure all ac output voltages. 508.1.3.1.2 Test. a. Start and operate the generator set at no load. b.
Adjust a regulated phase voltage (line-to-neutral) to rated voltage. c. Read and record the generator frequency, all line-to-neutral voltages, and all line-to-line voltages. d. Repeat steps a thru c above at each of the other voltage connections and frequencies specified in the procuremen t. e. If additional load conditions, other than no load, are specified in the procurement document, repeat steps a thru d above for all specified load conditions maintaining balanced loads (both resistive and reactive). 508.1.3.2 Procedure II. (Generator with separate excitation). 508.1.3.2.1 Preparation for test. winding). b. Connect the frequency inter to one of the armature coils of the generator. a.
Completely isolate the generator windings (armture coils and field Method 508.1d 1