Downloaded from https://www.everyspec.com MIL-STD-705C 410.1.4 Results. A curve of genera tor terminal voltage (vertical axis) versus exciter field current (and generator field current, if applicable) (horizontal axis) shall be plotted. If the knee of the curve is not well defined, repeat 410.1.3.2 taking additional readings as needed to better establish this portion of the curve. This curve is defined as the open circuit saturation curve (figure 410.1-II). Compare the results with the procurement d ocument requirmen ts. 410.1.5 Procurement d ocument requirements. The following items must be specified in the individual procurement document. a.
Voltage connection(s) and frequency(ies) at which this method is to be performed. b. Maximum value of no load exciter field current, if applicable. c. Maximum value of no load genera tor field current, if applicable. Method 410.1b 2