Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 602.1b VOLTAGE MODULATION TEST 602.1.1 General. If the peak value of a voltage wave is not constant but varies with time, the wave is considered to be voltage modulated. In many cases, the rate at which the peak value varies is so rapid or the magnitude of variation so small that the modulation cannot be detected by observation of a voltmeter. Voltage modulation can affect the operation of the generator set as well as some types of electrical equipment. 602.1.2 Apparatus. Instrumentation for measuring load conditions shall be as described and illustrated in MIL-HDBK-705.
In addition, a fast writing oscilloscope having a flat bandwidth of dc to 5 MHz, minimum, and single sweep features (Tektronix Model 556, or equal) equipped with a centimeter marked graticule and an oscilloscope camera will be required. The circuit illustrated in figure 602.1-I will also be required. The two zener diodes CR 1 and CR 2 are a matched pair with nominal rating of 170 volts; zener voltage of the two diodes shall be determined by test and shall not differ by more than 0.3 volts. A continuously variable autotransformer and isolation transformers will be needed. The continuously variable autotransformer shall be selected such that the following will apply: a.
There will be negligible saturation of the magnetic circuits. To achieve this requirement, the autotransformer rated input voltage shall be at least 125 percent of the maximum voltage which will be applied to its input terminals during this test. b. The distortion of the output shall not be more than 0.5 percent higher than at the input. c. The winding resistance will be not greater than 50 ohm. The same requirements shall apply for the isolation transformers at the input voltages indicated in figure 602.1-II. 602.1.3 Procedure. 602.1.3.1 Preparation for test. a. Connect the load apparatus in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10. b.
Operate the set at rated frequency and voltage at no load. c. Connect the specific voltage(s) to be tested to the modulation test box as shown in figure 602.1-II. The voltmeter shown shall be a rms indicating meter in accordance with MIL-HDBK-705, method 101.1. d. Compensate the oscilloscope probe in accordance with the manufacturer’s instruction. e. Verify the accuracy and frequency response of the oscilloscope by inserting a square wave signal of known value into the probe. Check all calibrated ranges to be used in this test. Method 602.1b 1