Downloaded from https://www.everyspec.com MIL-STD-705C 1. The prescribed steady state voltage bandwidth, extended to the point at which the voltage trace leaves the prescribed steady state band, shall be considered as the time at which the transient conditions begin. The point at which the voltage trace enters and remains within the prescribed band after a load change shall be considered as the point at which stabilization begins. Measure the distance (in inches) on the chart from the point where the voltage trace leaves the prescribed steady state band to the point where it reenters and remains within the prescribed voltage band for the next load condition.

Divide this distance by chart speed (in inches per second). This will give the voltage recovery time, in seconds. 2. 3. e. Determine the voltage regulation for all load changes (e. g. rated load to no load, 1/2 rated load to no load, no load to 1/4 load, etc.) as follows: 1. Using the indicating voltmeter readings subtract the load value of voltage from the no load value for each load changes (e.g. step 1 to step 2). (For voltage regulators utilizing single-phase voltage sensing, the value of voltage in the sensed phase only shall be used in the above calculations. For voltage regulators utilizing multi- phase voltage sensing, the average value of the sensed voltage shall be used.) 2.

Convert each of the values obtained in step 1 above to a percentage of rated by dividing by the rated voltage and multiplying by 100. This is the voltage regulation expressed in percent. 608.1.4.2 Repeat 608.1.4.1 substituting frequency for voltage. 608.1.4.3 requirements Compare the results tabulated of the procurement document. in 608.1.4.1 and 608.1.4.2 with the 608.1.5 Procurement document requirements. The following items must be specified in the individual procurement document: a. Frequency 1. Maximum allowable short-term stability bandwidth or deviation in percent of rated frequency. 2. Maximum allowable recovery time. 3. Maximum allowable overshoot and undershoot. 4.

Frequency(ies) at which this method is to be performed. 5. Maximum allowable regulation. b. Voltage 1. Maximum allowable short-term stability bandwidth or deviation in percent of rated voltage. 2. Maximum allowable recovery time. 3. Maximum allowable overshoot and undershoot, if applicable. 4. Voltage connection(s) at which this method is to be performed. 5. Maximum allowable regulation. Method 608.1b 5