Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 608.2a FREQUENCY AND VOLTAGE STABILITY TEST (LONG-TERM) 608.2.1 General. The generator-regulator-exciter combination must be capable of maintaining constant voltage and the engine-governor combination must be capable of maintainig constant speed for constant loads over long periods of time. Frequency stability describes the tendency of the frequency to remain at a constant value at a constant load. Generally, the instantaneous value of frequency is not constant but varies randomly above and below a mean value.
Stability may be described as either short-term or long-term stability depending upon the length of time that the frequency is observed. Another term, bandwidth, describes the limits of these variation. Bandwidth is expressed as a percentage of rated frequency of the generator set. Voltage stability is described similarly. 608.2.2 Apparatus. Instrumentation for measuring load conditions, field voltage and current, and ambient temperatures shall be as described and illustrated in MIL-HDBK-705. In addition, recording meter(s) shall be as described and illustrated in MIL-HDBK-705, methods 101.1 and 104.1 unless otherwise specified in the procurement document. 608.2.3 Procedure.
608.2.3.1 Preparation for test. a. Connect the load and field instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10 for the applicable voltage connection and frequency. Unless otherwise specified, connect the signal input of the recording meter(s) to the convenience receptacle of the set or to the generator coil which is used as the voltage sensing input to the voltage regulator. (Power the recording meter(s) from the commercial utility.) b. The following items shall be recorded on both the data sheets and the recording chart(s): 1. The date 2. The serial number(s) of the recording meter(s) 3. Generator set identification 4.
Recording chart speed(s) 5. Data reading number 608.2.3.2 Test. a. Start and operate the generator set and allow the set to stabilize at rated load, rated voltage and rated frequency. During this period operate the recording meter(s) at a chart speed of not less than 6 inches per hour, and record all instrument readings include thermal instrumentation at minimum intervals of 10 minutes. If necessary, Method 608.2a 1