Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 614.1b VOLTAGE AND FREQUENCY REGULATION TEST (FOR GENERATOR SETS) 614.1.1 General. The frequency regulation (sometimes referred to as droop) of a generator set is the maximum difference between the no load value of frequency and the value at any load up to and including rated load. This difference is expressed as a percentage of the rated load frequency of the generator set. The voltage regulation is expressed similarly except that the rms value of voltage is used. Frequency stability describes the tendency of the frequency to remain at a constant value at a constant load.

Generally, the instantaneous value of frequency is not constant but varies randomly above and below a mean value. Stability may be described as either short-term or long-tern depending upon the length of time that the frequency is observed. Another term, bandwidth, describes the limits of these variations. Bandwidth is expressed as a percentage of the rated frequency of the generator set. Voltage stability is described similarly. 614.1.2 Apparatus. Instrumentation for measuring load conditions, field voltage and current, and ambient temperature shall be as described and illustrate in MIL-HDBK-705. 614.1.3 Procedure. 614.1.3.1 Preparation for test. a.

Connect the load and instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10 for one voltage connection and frequency specified in the procurement document. b. Disconnect or otherwise render inoperative the cross current compensation circuits, if provided. 614.1.3.2 Test. a. Start and operate the generator set at rated voltage. Adjust the engine governor so that the frequency regulation is within the specified limits. b. Operate the generator set and allow the set to stabilize at rated load, voltage and frequency. During this period record all instrument readings including ambient temperature at minimum intervals of 10 minutes.

If necessary, adjustments to the load, voltage and frequency may be made to maintain rated load at rated voltage and frequency. Adjustments to the voltage and frequency shall be limited to those adjustments available to the operator, specifically adjustments to the voltage and frequency adjust devices. On sets utilizing a droop-type frequency control system as the prime speed control, the frequency and droop portions of the control may be adjusted. No other adjustments to the voltage and frequency control systems shall be made unless permitted by the procurement document. Adjustments to the load, voltage or frequency controls shall be recorded on the data sheet at the time of adjustment.

Method 614.1b 1