Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 412.1b ZERO POWER FACTOR SATURATION CURVE TEST 412.1.1 General. The zero power factor saturation curve is used by design engineers in injunction with the short-circuit and open-circuit saturation curves to determine certain performance characteristics of the generator under various load conditions. The family of generator saturation curves can be used to approximate the generator field current for any load condition. 412.1.2 Apparatus. Instrumentation for measuring load renditions and generator field voltage and current shall be as described and illustrated in MIL-HDBK-705.

In addition, a prime mover capable of maintaining constant rated speed of the generator under all load conditions of this method within ±1 percent and a source of dc power for generator excitation shall be required. Instruments for measuring the field current and terminal voltage shall have an accuracy of ± 0.5 percent, of reading or better. The power factor inter used shall be capable of indicating power factor to 0.3 lagging. 412.1.3 Procedure. 412.1.3.1 Prepara tion for test. a. Mechanically connect the prime mover to the generator and provide the external excitation supply to the generator. b.

Connect the load and field instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, for the voltage connection and frequency specified in the procurement document. 412.1.3.2 Test. a. Start and operate the prime mover such that the generator is operating at rated speed with zero excitation. Adjust the low power factor load to minimum reactance. NOTE: During all portions of this method the power factor of the load shall not exceed 0.40 and shall not be less than 0.30. Load current on polyphase generators shall be balanced. b. Increase the field current until the generator is supplying rated load current. Record all instrument readings.

Increase the load slightly, then increase the field current until the generator is again supplying rated load current. Adjust the excitation of the generator to approximately 20 percent rated voltage while maintaining c. d. e. f. the load current constant at the rated value. Record all instrument readings. Repeat steps d and e above to obtain at least seven equally spaced steps of terminal voltage up to and including 130 percent of rated voltage (unless otherwise specified in the procurement document). All readings shall be taken without interruption. Method 412. 1b 1