Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 620.4b VOLTAGE UNBALANCE TEST (THREE WIRE, SINGLE PHASE) set must have the capability to maintain balanced voltages to the system when an unbalanced load is applied. Voltage deviations from rated voltage affect single phase loads. Lights and single phase motors may have either too low or too high a voltage 620.4.1 General. A generator impressed on them for either efficient or safe operation. 620.4.2 Apparatus. Instrumentation for measuring temperature shall be as described and illustrate in load conditions MIL-HDBK-705. and ambient 620.4.3 Procedure.
instrumentation accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 620.4.3.1 Pre paration for test. Connect the load in 205.1.10 for one voltage connection and frequency specified in the procurement document. Note that only one voltmeter shall be used to measure all voltages and this voltmeter shall have an accuracy of ±0.5 percent of the reading or better. 620.4.3.2 Test. frequency, and under control of the voltage regulator. Record all instrument readings. b. Apply the specified load between terminals L 1 -L 0 , L 2 -L 0 , and L 1 -L 2 in a. Start and operate the generator set at rated voltage, no load, rated turn.
Record all instrument readings at each load condition (figure 620.4-I). 620.4.4 Results. a. Express the greatest difference between the two line-to-neutral voltages as a percent of rated line-to-neutral voltage. Compare this difference expressed in percent with the maximum allowable difference specified in the procuremen t document. b. 620.4. 4.1 Sample calculations. L 1 -L 0 = 118.0 volts L 2 -L 0 = 122.0 volts Voltage Difference = 4 volts Rated Line to Neutral Voltage = 120 volts 4.0 x 100 = 3.33 percent 120.0 Method 620.4b 1