Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 640.1d MAXIMUM POWER TEST (FOR GASOLINE AND DIESEL GENERATOR SETS) 640.1.1 General. The maximum power of a generator set is a function of the ambient conditions (temperature and altitude) and the mechanical condition of the engine at any particular time. 640.1.2 Apparatus. Instrumentation for measuring load conditions, field voltage and current, pressures temperatures shall be as described and illustrated in MIL-HDBK-705. 640.1.3 Procedure. CAUTION: This procedure subjects the generator set to a severe overload which may be damaging if maintained for too long a period of time. 640.1.3.1 Preparation for test. a.
Connect the load and instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10 for one voltage connection and frequency specified in the procurement document. b. Install appropriate thermocouples to measure the following temperatures: (NOTE: Not all sets will require instrementation of all of the listed items. The list contains items normally instrumented. However, some sets may require additional thermal instrumentation). 1. Engine coolant (engine outlet and met). 2. Spark plug(s). 3. Exhaust gas(es) [the exhaust manifold(s) shall be drilled and tapped as close as possible to the combustion chamber(s).] 4. Lubricating oil sump. 5.
Engine combustion air in (located at the inlet of the intake manifold). c. Install appropriate pressure instrumentation to measure the following items: 1. Exhaust pressure (combined exhaust gases in exhaust manifold). 2. Intake air manifold pressure (between air filters and manifold). d. Obtain and record the barometric and water vapor pressures (see MIL-HDBK-705, method 220.2). e. On generator sets having more than one power output system; e.g. high voltage ac and low voltage dc (disregard the battery charging system) or two ac systems of different frequencies, maintain the system with the lowest power rating at rated load for all parts of this test.
The load in the system with the highest power rating is then varied as indicated below to determine the maximum power of the set. Method 640.1d 1