Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 640.4a MAXIMUM POWER TEST FOR GASOLINE AND DIESEL, GENERATOR SETS (PRODUCTION SETS) 640.4.1 General. The maximum power of a generator set is a function of the ambient conditions (temperature and altitude) and the mechanical condition of the engine at any particular time. 640.4.2 Apparatus. Instrumentation for measuring load conditions. temperatures and pressures shall be as described and illustrate in MIL-HDBK-705. 640.4.3 Procedure. CAUTION: This procedure subjects the generator set to a severe overload which may be damaging if maintained for too long a period of time. 640.4.3.1 Preparation for test. a.
Connect the load and instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10 for the voltage connection and frequency specified in the procurement document. b. Install appropriate thermocouples to measure the following temperatures. 1. Lubricating oil sump. 2. Engine combustion air in (located at the inlet of the intake manifold). c. Obtain and record the barometric and water vapor pressures (see MIL-HDBK-705, method 220.2). d.
On generator sets having more than one power output system, e.g., high voltage ac and low voltage dc (disregard the battery charging system) or two ac systems of different frequencies, maintain the system with the lowest power rating at rated load for all parts of this test. The load on the system with the highest power rating is then varied as indicated below to determine the maximum power of the set. e. Bypass the set circuit interrupter if required. f. Connect the set to a source of fuel as required by the procurement document. 640.4.3.2 Test. a. Start and operate the generator set and allow it to stabilize at rated load, rated voltage and rated frequency (speed).
During this period readings of all instrumentation including thermal instrumentation shall be recorded at minimum intervals of 10 minutes. If necessary, adjustments to the load, voltage and frequency may be made to maintain rated load at rated voltage and rated frequency. However, adjustments to Method 640.4a 1