Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 651.2d JUDGING OF COMMUTATION TEST (DC SETS) 651.2.1 General. Excessive sparking at the commutator of the brushes and will damage the commutator. will shorten the life 651.2.2 Apparatus. Instrumentation for measuring load described and illustrated in MIL-HDBK-705. conditions shall be as 651.2.3 Procedure. 651.2.3.1 Preparation for test. a. Examine the brushes for wear, pitting, or other signs of unsatisfactory service. Record these conditions on the data sheet (see figure 651.2-II). b. Connect the load instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10. 651.2.3.2 Test. a.
Start and operate the generator set at rated voltage, rated speed and at rated load for at least 30 minutes. b. Compare the observed sparking of each brush with the chart shown in figure 651.2-I using at least two observers. c. Record the chart pattern number which most closely corresponds to the sparking observed at each brush. d. Repeat steps b and c above at each load voltage connection and frequency condition specified in the procurment document. e. After shutdown, the commutator and brushes shall be examined for wear, pitting, or other signs of unsatisfactory conditions on the data sheet. service. Record these 651.2.4 Results. Compare the results with the requirements.
procurement document 651.2.5 Procurement document requirements. The specified in the individual procurement document. following items must be a. Load conditions at which this method is to b. Acceptable values of sparking pattern (see be performed. figure 651.2-I). Method 651.2d 1