Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 655.1a DC CONTROL TEST 655.1.1 General. In certain instances, it may be necessary to operate a generator set with a value of dc control voltage other than the nominal rated value. 655.1.2 Apparatus. Instrumentation for measuring load conditions shall be a described and illustrated in MIL-HDBK-705.
A recording meter(s) as described and illustrated in MIL-HDBK-705, methods 101.1 and 104.1 (unless otherwise specified in the procurement document) for recording voltage and frequency, an oscilloscope (and camera) as described in MIL-HDBK-705, method 106.1, paragraph 106.1.2 and a dc voltmeter and ammeter as described and illustrated in MIL-HDBK-705, methods 101.1 and 102.1 will be required. 655.1.3 Procedure. 655.1.3.1 Preparation for test. a. Connect the load and instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10.
Unless otherwise specified, connect the signal input terminals of the recording meter(s) to the convenience receptacle of the set or to the generator coil which is used as the voltage sensing input to the voltage regulator. b. Locate a point in the dc bus which supplies the dc control power for the generator set. Connect a dc ammeter at this point to indicate the total current drawn by the dc control circuitry and place a dc voltmeter to indicate the bus voltage with respect to ground. CAUTION: Make sure that the ammeter does not read the starting motor solenoid current or the battery charging current. c. Disconnect the set batteries. 655.1.3.2 Test. a.
Using fully charged slave batteries and cable, start the set. Record on the data sheet whether or not the set started (see figure 655.1-I). b. If the set is required to have reverse polarity protection, shut the set down, disconnect any belt driven battery charging alternator, and remove the slave cable. Reverse the battery polarity and attempt to restart the set. Record if the set started and whether any damage occurred. If the set is equipped with fuse protection, check the fuse before proceeding with step c below and record if fuse replacement was necessary. Reconnect the belt-driven alternator, if applicable. c.
Reconnect the slave batteries (with correct polarity), then start and operate the generator set at rated voltage, rated frequency and rated load. Method 655.1a 1