Downloaded from https://www.everyspec.com MIL-STD-705C 731.1.3.2 Test. a. For sets with gasoline engines, start the cold room and when the ambient temperature has reached approximately 0 °F (-17.7 °C) open the auxiliary fuel container and connect it to the genera tor set through the auxiliary fuel connection. (Note: The parameters of arctic fuel at temperatures above 0 °F (-17.7 °C) necessitates storing the fuel in sealed containers.) Fill and label a small container with a sample of the fuel used. Place this sample alongside samples of fuel, lubrication oil, and coolant taken previously, in preparation for test, in a location in the cold chamber where they may be observed.
For sets with gasoline engines, start and operate the set for approximately 15 minutes at no load to allow the arctic fuel to thoroughly circulate. Then shut down the set (see figure 731.1-I). Expose the generator set to an ambient temperature of -40 °F (-40 °C) or as specified in the procurement document until the temperature of all components of the set stabilize at this value. During all parts of this method, none of the eight ambient temperature thermocouples shall read warmer than the specified extreme-cold temperature. Expose the generator set to an ambient temperature of -80 °F (-62.2 °C) until the temperature of all components of the set stabilize at this value.
Maintain the ambient temperature at -80 °F (-62.2 °C) for 24 hours after the stabilization is attained. During this period, inspect the set for evidence of distortion or cracking of the components, and leaks in fuel, lubrication, and cooling systems. Raise the ambient temperature to -40 °F (-40 °C) and maintain this temperature until the temperature of all components of the set stabilize at this value. Raise the ambient temperature to normal ambient temperature and maintain this temperature until the temperature of all components of the set stabilize at this value. Drain the arctic fuel, lubricating oil, and coolant from the set. Do not remove fuel stra iners, filters, gaskets, etc.
Refill the set with normal ambient fuel, lubricating oil, and coolant. b. c. d. e. f. g. h. Start and operate the generator set at idle speed (reduced speed if no idle speed is attainable), inspect the set for leaks, faulty operation, etc. After the unit has been warmed up, increase speed to rated. Inspect the set again and then apply rated load and perform method 608.1, Frequency and voltage Regulation, Stability and Transient Response Test (Short Term). NOTE:
This method may be combined with method 701.1, Starting and Operating Test (Extreme Cold) in which case, steps e, f, g, and h of this method should be deleted and after stabilization at -80 °F (62.2 °C) the ambient temperature should be raised to -65 °F (-53.8 °C) and the set stabilized at this value before proceeding with method 701.1. 731.1.4 Results. Compare the results with the procurement document requirements. Method 731.1c 3