Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 732.1c STORAGE TEST (EXTREME HOT, +160 °F) 732.1.1 General. The genera tor set must be capable of storage without damage in extreme high temperature environments. 732.1.2 Apparatus. Instrumentation for measuring load conditions, field voltage and current, set and ambient temperatures shall be as described and illustrated in MIL-HDBK-705. 732.1.3 Procedure. 732.1.3.1 Preparation for test. a. Install appropriate thermocouples to measure the following temperatures. (Note: Not all sets will require instrumentation of all of the listed items.
This list contains item normally instrumented; however, some sets may require additional thermal instrumentation.) The thermal instrumentation shall be installed in accordance with the instructions in MIL-HDBK-705, method 202.1. 1. 2. 3. 4. Engine coolant (engine outlet and inlet). Fuel (discharge side of fuel pump and at fuel source). Spark plug(s) (gasoline engines). Exhaust gases (the exhaust manifold(s) of reciprocating engines shall be drilled and tapped as close as possible to the combustion chamber(s). For gas turbine engines, thermocouples shall be located in the tailpipe approximately one turbine wheel diameter downstream from the last turbine stage).
Lubricating oil (sump and gallery). Oil cooler (inlet and outlet). Hydraulic oil (sump). Engine combustion air in (located at the inlet of the intake manifold). Cooling air into the radiator (four thermocouples equally spaced around the circumference of the area swept by the fan blades). Generator cooling air (inlet and outlet). Generator stator from (top and bottom, outside). Generator exciter (stator housing for rotating exciters, transformers for static exciters). Generator voltage regulator (ambient air inside). Control panel cubicle (ambient air inside). Relay and control boxes (ambient air inside). Battery electrolyte (one thermocouple for each battery, inside a central battery cell).
Average ambient air temperature (MIL-HDBK-705, method 202.1). Air entering generator set for housed sets. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. b. Connect the load and field instrumentation in accordance with the applicable figure of MIL-HDBK-705, method 205.1, paragraph 205.1.10. Method 732.1c 1