Department of Defense MIL-STD-705C — MIL-STD-705C Generator Sets Engine-Driven Test Methods Standard PDF

Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 421.1b DIRECT-AXIS SYNCHRONOUS REACTANCE TEST 421.1.1 General. The direct-axis synchronous reactance is the ratio determined by dividing the field current during a sustained symmetrical short circuit, at rated frequency required to produce rated armature current, by the value of the field current at the air–gap line of the open circuit saturation curve, at rated voltage and frequency. NOTE: The definition above is actually that of the per unit direct-axis synchronous impedance.

However, this definition is used to a great extent in electrical literature and because the resistance of the machine is so small compared to the reactance, the error in using the impedance value instead of the reactance value is negligible. 421.1.2 Apparatus. Instrumentation for measuring terminal voltage, generator speed, exciter field voltage and current (generator field voltage and current, if if applicable), and line current shall be as described and illustrated in MIL-HDBK-705. In addition, a prime mover having a steady state speed not greater than ±1 percent of rated speed and a separate, variable dc source for excitation shall be required.

Electrical instrumentation used for this test shall have an accuracy of ±0.5 percent of reading or better. 412.1.3 Procedure. a. Perform test method 410.1 (Open Circuit Saturation Curve Test). (Measure the generator field current). b. Perform test method 411.1 (Synchronous Impedance Curve Test). 421.1.4 Results. a. From the syrdronous impedance curve (the short circuit saturation curve), determine the field current required to produce rated armature current for a sustained symmetrical short circuit at the generator terminals. In figure 421.1-I this value is represented by the distance I fsi .

From the air-gap line of the open circuit saturation curve (the extended straight line part of the curve, see figure 421.1-I) determine the field current which corresponds to the rated voltage. In figure 421.1-I this value is represented by the distance I fg . b. c. Compute the direct-axis synchronous reactance by dividing the value obtained in step a above by the value obtained in step b above. This computation is representd by the following formula: Method 421.1b 1