Downloaded from https://www.everyspec.com MIL-STD-705C 422.1.4.2 Compute the negative-sequence impedance from the date obtained in this method using the following formula: Z 2 (in percent) = EI RP X 100 1.732IV RP Where: Z 2 = negative-sequency impedance E = Voltage between the shorted terminals and the third line terminal V RP = Rated phase voltage I RP = Rated phase current I = ac current in amperes 422.1.4.3 Compare these results with the procurement document requirements. 422.1.5 Procurement d ocument requirements. The following items must be specified in the individual procurement document: a.
The voltage connection (must be three-phase wye) and frequency at which this method is to be performed. b. The maximum, minimum or range of allowable negative–sequence reactance, or negative-sequence impedance if applicable. Method 422.1b 2