Department of Defense MIL-STD-705C — MIL-STD-705C Generator Sets Engine-Driven Test Methods Standard PDF

Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 423.1b ZERO-SEQUENCE REACTANCE TEST 423.1.1 General. Zero-sequence reactance determine the performance of three-phase wye load conditions. is used by design engineers to connected generators under various 423.1.1 Apparatus. Instrumentation for measuring line-to-line voltage, line current, generator speed and field current shall be as described and illustrated in MIL-HDBK-705. In addition a separate, variable source of dc power for generator excitation and a prime mover shall be required. Electrical instrumentation for this test shall have an accuracy of ±0.5 percent of reading or better. 423.1.3 Procedure.

423.1.3.1 Preparation for test. a. Mechanically connect the generator to the prime mover and provide the external excitation supply to the generator. b. Connect the instrumentation in accordance with figure 423.1-1 for one “wye” voltage connection and frequency specified in the procurement document. 423.1.3.2 Test. a. Start and operate the prime mover such that the speed and with zero field current. b. Adjust the field current such that the ammeter, generator is at rated which short-circuits two generator phases to neutral, indicates a reading equal to three times the rated phase current. c. Record all instrument readings (see figure 423.1-II). CAUTION:

To prevent serious overheating of the generator, the field current shall be reducded to zero and the generator shut down immediately following the reading of the instruments. 423.1.4 Results. 423.1.4.1 Compute the zero-sequence reactance using the following formula: X o (in percent) = E a I rp X 100 I n V R P Method 423.1b 1