Department of Defense MIL-STD-705C — MIL-STD-705C Generator Sets Engine-Driven Test Methods Standard PDF

Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 302.1b HIGH POTENTIAL TEST CAUTION: OBSERVE SAFETY REGULATIONS. The voltages used in this method are dangerous to human life. Contact with the leads or the windings under test may cause severe, and possibly fatal, shock. Arrange the high voltage leads so that they are not in a position to be accidentally touched. Keep clear of all energized parts. Always reduce the test voltage to zero and ground the winding under test before making any mechanical or electrical adjustments on the equipment. When grounding windings which have been tested, always connect the connection wire to ground first, and then to the winding.

Never perform this test without at least one other person assisting. The genera tor frame shall be securely grounded to the building ground or earth ground. 302.1.1 General. The genera tor insulation materials must be capable of withstanding, without damage, voltages higher than rated for definite periods of time to preclude damage during transient loading and short circuit conditions. This test should be performed after the equipment is completely assembled so that damage to the insulation which might have occurred during manufacture and assembly will be detected. 302.1.2 Apparatus. A variable alternating current, high voltage, current- limited power source shall be required.

302.1.3 Procedure. 302.1.3.1 Prepara tion for test. a. Adequately ground the high potential apparatus to a solid electrical ground in accordance with instructions accompanying the apparatus. Also, enerator set and all windings of the connect the main frame of the g generator, not under test, to the same ground. Unless rectifiers and semiconductors are specifically designed to withstand the specified test voltage they should be removed or disconnected from the circuit along with any radio suppression capacitors prior to conducting the tests. Raise, or remove, brushes from commutator and slip rings, if applicable.

Isolate the generator power output windings, the generator field windings, and the exciter armature and field windings if a part of the set. This is accomplished by disconnecting the various windings from the associated control circuits or other connections. Static excitation systems feeding the field excitation from the ac generator shall be tested with all rectifiers and capacitors disconnectd, unless such rectifiers and capacitors are designed to withstand the specified test voltage. Connect the high voltage lead from the test apparatus to the winding or circuit under test. All other windings and circuits must be securely connected to ground. b. c. d. e. Method 302.1b 1