Downloaded from https://www.everyspec.com MIL-STD-705C METHOD 426.1b DIRECT-AXIS SUBTRANSIENT REACTANCE TEST 426.1.1 General. The direct-axis subtransient reactance is used by design engineers to determine the necessary interrupting capacity of the set circuit interrupter. 426.1.2 Apparatus. Instrumentation for measuring load conditions, field voltage and current shall be as described and illustrated in MIL-HDBK-705.
In addition an oscilloscope with sufficient galvanometers having a flat frequency response (flat within ±5 percent) from dc to 3,000 Hz, a non-inductive shunt, a timing wave source, a short circuiting switch, a separate, variable dc source for generator excitation and a prime mover capable of maintaining the generator speed within ±1 percent of rated speed under all load renditions of this method shall be required. Electrical instrumentation for this test shall have an accuracy of ±0.5 percent of reading or better. 426.1.3 Procedure. a. b. Perform method 425.1, Direct-Axis Transient Reactance Test.
On the same graph as plotted for method 425.1, plot an additional line as shown in figure 426.1-I. The procedure for plotting this line is as follows: 1. Ascertain the scale distance between the straight line (Curve “B”) and the curved line (Curve “A”) for at least three peak positions. Plot these distances on the respective peak lines. In the example, Curve “A” is 24 mm from Curve “B” on the No. 2 peak perpendicular. Similarly, at the 2.6 peak, the scale distance between the two curves is 7.5 mm. At the No. 3 peak, the distance is 3.5 mm. Draw a straight line through these points. In the example, this line is identified as Curve “C”. 2. 3. c.
Read the value in mm (or the unit used in measuring the distances in step b above) where the the Curve “C” crosses the t = 0 line. In the example, this crossing is at 264 mm. Using the following formula compute the direct-axis subtransient d. reactance, X" d . X"d (in percent) = I RATED x 100 ( i ' t=0 i t=0 + i s s ) I s s i s s Method 426.1b 1