Delta Electronics MS300 — 03 Analog Input / Output Parameters

Chapter 12 Descriptions of Parameter Settings  MS300  Default: -100.00 Settings -100.00–100.00 %  When you set the negative voltage AVI to the Frequency command, -100% corresponds to Fmax (valid when Pr.03-28 sets as -10–10 V) (Pr.01-00 Maximum Operation Frequency) and the motor runs in the reverse direction.  The requirement for these three parameters (Pr.03-69, Pr.03-71 and Pr.03-73) is Pr.03-69 Pr.03-71 have no limits. There is a linear calculation between two points.  The output percentage becomes 0 % when the negative voltage AVI input value is lower than the lowest point setting. Example:

If Pr.03-69 = -1 V; Pr.03-70 = 10%, then the output becomes 0 % when the AVI input is ≥ - 1 V. If the AVI input swings between -1 V and -1.1 V, drive’s output frequency oscillates between 0 % and 10 %. 12.1-03-22 Negative AVI Proportional Highest Point