MultiPlus-II 2x120V Ripple alarm The inverter has switched off due to excess ripple voltage on the battery terminals. The "overload" and "low battery" LEDs are both on. Bulk charging The AC input voltage is switched through and the charger operates in bulk mode. The "bulk" LED is on. BatterySafe The mains voltage is switched through and the charger is on. However, the set absorption voltage has not yet been reached. The "bulk" and "absorption" LEDs are both on. Absorption charging The mains voltage is switched through and the charger operates in absorption mode. The "absorption" LED is on. Float charging The mains voltage is switched through and the charger operates in float mode.
The "float" LED is on. Equalize charging The mains voltage is switched through and the charger operates in equalize mode. The "bulk" and "absorption" LED are both blinking. Page 8 Operation