Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 4.4. Firmware

MultiPlus-II inverter/charger Australia If this setting is ‘on’, the MultiPlus-II will start supplying extra power at a low generator output level and gradually allow the generator to supply more until the set current limit is reached. This allows the generator engine to get up to speed. This setting is also often used for ‘classical’ generators that respond slowly to sudden load variation. Weak AC This setting is for use with generators. Strong distortion of the input voltage can result in the charger hardly operating or not operating at all. If WeakAC is set, the charger will also accept a strongly distorted voltage at the cost of greater distortion of the input current. Recommendation:

Turn WeakAC on if the charger is hardly charging or not charging at all (which is quite rare!). Also, turn on the dynamic current limiter simultaneously and reduce the maximum charging current to prevent overloading the generator if necessary. When WeakAC is on, the maximum charge current is reduced by approximately 20%. BoostFactor Programmable relay Change this setting only after consulting with Victron Energy or with an engineer trained by Victron Energy! The relay can be programmed for all kinds of other applications, for example, as a starter relay for a generator. Auxiliary AC output (AC-out-2) This output is intended for non-critical loads.

It is directly connected to the AC input and is included in the current measurement circuit to enable PowerAssist. 4.4. Firmware For information on firmware and for instructions on how to view the firmware version refer to the VictronConnect configuration guide for VE.Bus products document. It is not necessary to update the unit to the latest firmware version. Stable systems should be left with their current firmware. Page 16 Configuration