MultiPlus-II inverter/charger Australia 11.3. Generator connection This diagram applies when the sytem is used with a generator connected to the AC input. With this configuration, the inverter’s internal ground relay is not used and remains open. The installation must therefore have a permanent MEN connection located at the Main Switchboard (MSB). This provides the required neutral-to-earth reference and ensures correct RCD operation. Install a neutral link between the AC-In neutral and the AC-Out neutral, as shown in the diagram below. Make the connections within the switchboards. The following grid code should be selected in VE.Configure: Australia X:
AS/NZS 4777.2:2020+A1+A2 stand alone app. M (with N-bypass) Page 31 Appendix