Victron Energy MultiPlus-II 48V - 3k, 5k - GX — 11.7. Temperature compensation

MultiPlus-II inverter/charger Australia The voltages in the above table are for a 12V battery bank. To arrive at 48V battery bank voltages, multiply the 12V voltages by a factor of four. 4-stage charging: Bulk Entered when charger is started. Constant current is applied until nominal battery voltage is reached, depending on temperature and input voltage, after which constant power is applied up to the point where excessive gassing starts. This is at 14.4 V for temperature compensated for lead acid batteries. Battery Safe The voltage applied to the battery is raised gradually until the set absorption voltage is reached. The Battery Safe Mode is part of the calculated absorption time.

Absorption The absorption period is dependent on the bulk period. The maximum absorption time is the set Maximum Absorption time. Float Float voltage is applied to keep the battery fully charged. Storage After one day of float charge, the output voltage is reduced to the storage level. This is 1.2 V. This will limit water loss to a minimum when the battery is stored for the winter season. After an adjustable time (default = 7 days), the charger will enter Repeated Absorption mode for an adjustable time (default = one hour) to ’refresh’ the battery. 11.7. Temperature compensation Default output voltages for Float and Absorption are at 25 °C for 12 or 24V battery bank. Page 34 Appendix