MultiPlus-II inverter/charger Australia 3. Installation This product may only be installed by a qualified electrician. 3.1. Location The product is rated IP21. Therefore, it must be installed indoors, in a dry and well-ventilated area, as close as possible to the batteries. Ensure there is a clear space of at least 10 cm around the appliance for cooling. It can be installed in a conditioned or unconditioned environment; however, if installed in a hot environment, conditioning is recommended to avoid inverter power deration due to high ambient temperatures. Excessively high ambient temperature will result in the following: Reduced service life. Reduced charging current.
Never position the appliance directly above the batteries. Reduced peak capacity or shutdown of the inverter. The MultiPlus-II is suitable for wall mounting. A solid surface suitable for the weight and dimensions of the product must be available (e.g., concrete or masonry). For mounting purposes, a hook and two holes are provided at the back of the casing (see Appendix G). The interior of the product must remain accessible after installation. Try to keep the distance between the product and the battery to a minimum in order to minimise cable voltage losses. For safety purposes, this product should be installed in a heat-resistant environment.
You should prevent the presence of chemicals, synthetic components, curtains or other textiles, etc., in the immediate vicinity. Each system requires a method of disconnecting the AC and DC circuits. If the overcurrent protection device is a circuit breaker, it will also serve as the disconnect. If fuses are used, separate disconnect switches will be needed between the source and the fuses. To reduce the risk of fire, do not connect to an AC load centre (circuit breaker panel) with multiwire branch circuits. CAUTION – To reduce the risk of injury, charge only Lead Acid or LiFePO4-type rechargeable batteries. Other types of batteries may burst, causing personal injury and damage.
Do not try to recharge non-rechargeable batteries. Use of an attachment not recommended or sold by the marine unit manufacturer may result in a risk of fire, electric shock, or injury to persons Page 6 Installation