2 Installing the NB Unit and Connecting Peripheral Devices 2-4 Serial Communication Connection When connecting to a CJ Series Serial Communication Unit For CJ1W-SCU21/22 type (Both of port 1 and 2 are RS-232C ports) For CJ1W-SCU31/32 type (Both of port 1 and 2 are RS-422A/485 ports) (Unit version1.3) For CJ1W-SCU41/42 type (Port 1 is RS-422A/485 port and Port 2 is RS-232C port.) Settings for the DM Fixed Allocation Area of the CPU Unit Write settings directly to the [DM Fixed Allocation Area] of the CPU Unit (System Settings Area) with a peripheral tool (programming console or CX-Programmer).
After finishing the write-in, the settings can be activated through any of the methods of reconnecting the power supply, restarting the Unit, reactivating the communication port, executing the STUP instruction. It is the same when using RS-232C, RS-422A. The followings are the Channel Nos. and settings of the DM Fixed Allocation Area. m = DM30000 + 100 Ч Unit No. (CH) 2-4-3 Settings for each Unit *1 The communication speed should be set to the same value as that of the NB Unit. Settings for the NJ Series Set the Serial Communication Unit configuration below with peripheral tool (Sysmac Studio).
Under Configurations and Setup - CPU/Expansion Racks in the Multiview Explore, settings are existed. In the Serial Communication Unit settings, configure the following settings: NB-series Programmable Terminals Setup Manual(V107) 2-23 2 DM Fixed Allocation Area (CH) Write Value Setting Port 1 Port 2 m+10 8000 m+11 0000~000A (*1) m+13 0000 Item Set value Serial communications mode Host Link (FINS) Unit No. 0 Baud rate Set this to match the setting on the NB-series Unit. Data length 7 bits Parity Even Stop bit 2 bits