2 Installing the NB Unit and Connecting Peripheral Devices Setting Node Numbers 2-5 UDP Communication Connection NODE NO. Ч16 1 Ч16 0 Setting range 01 to FE (1 to 254 decimal) Set the upper digit using the left rotary switch and the lower digit using the right rotary switch. The factory setting is 01. The Node ID of the rotary switch here must be consistent with that of PLC in the “Communication Setting” dialog box for the actual project created in the NB-Designer. Setting Local IP Addresses For CS-series Ethernet Units, set the local IP address from the CX-Programmer or other Support Software for the CPU Unit. Refer to the SYSMAC CS/CJ Series Ethernet Unit Operation Manual (Cat. No.
W420) for details on setting methods. Ethernet Connectors 2-5-3 Host Types and Settings of Ethernet Unit CS1W-ETN21 This is the connector used to connect the twisted-pair cable to the Ethernet. • Electrical characteristics: Conforms to IEEE802.3 standards. • Connector structure: RJ45 8-pin modular connector (conforms to ISO8877). 1 8 Note 1 Always turn OFF the power to the PLC before setting the rotary switches. 2 Create I/O tables for the CPU Unit when setting the unit number for the first time or changing settings. CJ-series Ethernet Units:
CJ1W-ETN21 Setting the Front Panel Switches Setting Unit Numbers Always set the unit numbers so that the unit numbers of other CPU Bus Units mounted to the same CPU Unit are all unique. Use a small screwdriver to set the rotary switches, being careful not to damage them. The factory setting is 0. UNIT No. Setting range 0 to F NB-series Programmable Terminals Setup Manual(V107) 2-35 2 Connector Pin Signal name Abbreviation Signal direction 1 Send data + TD+ Output 2 Send data - TD- Output 3 Receive data + RD+ Input 4 Not used. - - 5 Not used. - - 6 Receive data - RD- Input 7 Not used. - - 8 Not used. - - CJ-series PLCs