Appendices A-3 RS-422A/485 Connections A-3-1 Grounding and Shielding of the Cables When performing communications using RS-422A/485, carry out the connections, shielding and grounding as follows: Grounding wiring The NB Unit has a functional grounding terminal (FG: ). A-3 RS-422A/485 Connections A-3-1 Grounding and Shielding of the Cables (1) Generally, make the grounding according to Fig. (a). • Connect the grounding terminals (GR) of the devices and the functional grounding terminal ( ), at only one point make a D-type grounding (Max. grounding resistance 100 Ω ). • Short-circuit the LG terminal and GR terminal of the PLC. • Use a cable with a minimum of 2 mm 2 for the grounding cable.
• For details about the connection methods, refer to the related communication Unit manuals. (2) As shown in Fig. (b), when the NB Unit, and noise source equipments such as motors and inverters, etc. are installed on the same panel, do not ground the NB Unit’s functional grounding terminal ( ). Shielding of RS-422A/485 Cables Be sure to shield the RS-422A/485 cables. Connect the grounding terminals (GR) of the devices and the functional grounding terminals ( ), at only one point make a D-type grounding (Max. grounding resistance 100 Ω ), carry out a single-end shielding according to Fig. (a).