Nucleo GX Manual 12.2. DVCC Requirements 1. Battery compatilibity For CAN-bus connected batteries, refer to the relevant page in the Battery Compatibility manual to see if enabling DVCC has been tested with your battery type and is supported. → Only enable DVCC if it is explicitly listed as supported for your battery type. If DVCC is not mentioned in notes relating to your battery, do not enable it. DVCC is fully supported and can be used without issue for: Lead-acid batteries (Gel, AGM, OPzS, etc.) Victron Lithium Smart with: VE.Bus BMS Lynx Ion + Shunt BMS Lynx Ion BMS Victron Lithium NG with:

VE.Bus BMS NG For systems with the Lynx Smart BMS or Lynx BMS NG, DVCC is automatically enabled and cannot be disabled. 2. Firmware versions Do not use DVCC if firmware requirements are not met. During commissioning, always install the latest available firmware. Once the system is running reliably, firmware updates are not required unless needed. If issues occur, the first step should be to update firmware. Required minimum firmware versions: Firmware compatibility warning – Error #48 Starting from Venus OS firmware v2.40, the GX device will display the warning:

Error #48 – DVCC with incompatible firmware This indicates that one or more connected devices are running firmware versions incompatible with DVCC. For further details on this error, refer to the Error codes chapter [159] . ESS system requirement If using an ESS system, ensure the ESS Assistant is version 164 or later (released November 2017), as earlier versions are not compatible with DVCC.

DVCC - Distributed Voltage and Current Control Page 107 Victron product Minimum firmware version Multi/Quattro 422 MultiGrid 424 Multi RS, Inverter RS, MPPT RS v1.08 GX device v2.12 VE.Direct MPPTs v1.46 VE.Can MPPTs with VE.Direct v1.04 Older style VE.Can MPPT Solar Chargers (with the screen) Cannot be used Lynx Ion + Shunt v2.04 Lynx Ion BMS v1.09 Lynx Smart BMS v1.02 Lynx BMS NG v1.10 Orion XS v1.00