Victron Energy Nucleo GX — 20.1.7. RV-C Fault and Error Handling

Nucleo GX Manual Tank meters will be translated into RV-C messages, carrying forward the existing tank ID/ VRM Instance numbers. 20.1.6. Instance Translation RV-C utilises Instances in several ways: DC Source Instance AC Line Device Instance (context dependent) Each usage of the Instance has a specific meaning, and a given device may at times utilise one or more of these instances. DC Source Instance In RV-C, a DC source is something that can generate and (optionally) store energy. Typically a battery but can also be a fuel cell or the output side of a DC contactor/disconnector.

A DC source can be thought of as a battery system and its associated physical bus, for example, the house battery, the DC bus bar and DC wiring. DC Source Instances are used to associate subsequent devices (e.g. a charger or an inverter) to the ‘DC bus’ it is connected to. In this way it is possible to map out how all devices are connected with regards to their DC bus via their DC Source Instance value (starter battery and its alternator, house battery and its chargers etc.). Note that in some cases (e. g. a DC-DC Converter or a Contactor), a device may be associated with two different DC Source instances.

For example, a DC-DC converter could be associated with the two different batteries to which it is connected, while a contactor could be associated with the battery to which it is connected; the DC bus on the load side of the contactor then has its own DC Source instance Though Victron is able to support more than one battery (a house and starter battery), the primary focus is on one battery. The dbus-rvc module will present the ‘primary’ battery to RV-C as ‘DC Source Instance = 1’ (house battery) information. If present, additional Victron sensing devices will be presented using DC Source Instances of 2. An example is the optional starter battery voltage sensing on SmartShunts.

AC Line AC line is much simpler, in that RV-C assumes a limited AC system, typically defined as Line 1 or Line 2. Victron supports 3-phase systems, which is not included in the RV-C specification. All installations with 3-phase systems are not supported by the dbus-RVC module and AC-related RV-C messages are suppressed. Device Instance Device Instance is a way to separate different physical devices of the same type. Example: if an installation contains two AC chargers attached to the same battery, each would be assigned a separate Device Instance while both would share the same DC Source Instance. Each charger would also be associated with an AC line, which may or may not be the same.

In this way the AC charger is fully described in how it is wired on the AC and DC side while being able to be uniquely identified through its Device Instance. Devices Instances are relevant within a given class of devices. An AC charger can define Device Instances 1 and 2, and these are unrelated to Device Instances 1 and 2 of a DC motor controller. With the exception of tank monitoring, Device Instances are hard coded as 1 for each specific device class unless specified otherwise in the PGN table. Because the AC charger has a hardcoded instance of 2, to allow coexistance with a inverter/charger with charger instance 1. 20.1.7. RV-C Fault and Error Handling RV-C fault reporting:

Fault conditions are reported using the DM_RV (0x1FECA) and J1939 DM01 (0x1FECA) DGNs. In release 1 the operational status bits, the yellow and the red light field are supported because they are stored in DSA. SPN is set to 0xFFFFFF during normal conditions, and 0x0 at any time a warning or fault condition exists in supported Victron equipment. FMI is set of 0x1F (Failure mode not available) at all times. This simple mapping allows external user displays to indicate an alarm or fault condition in a given Victron device, at which time the user should utilise Victron diagnostic aids for additional insight. Page 178 Appendix