beckhoff TwinCAT 2 — 5.3 Controller

TwinCAT NC Axis components The sample is parameterized with Kvs = 50, Kvf = 10 and Vdyn = 0,2. Position PID controller Controller parameters Numerical Control (NC) Basics 39 Version: 1.2 Parameter Data type Unit Description Position control: proportional factor Kv float >=0 [mm/s]/mm Proportional gain of the P component. Output velocity = pre-control velocity + Kv lag error. Position control: integral action time Tn float >=0 s Integral action time of the I component (integration time) Position control: rate time Tv float >=0 s Rate time of the real D component (D-T1 component). Position control: damping time Td float >=0 s Damping time of the real D component (D-T1 component).

OPERATION MODE: automatic offset calibration BOOL Activation or deactivation of the automatic offset calibration. The automatic offset calibration is only active in the range of the relative pre-control velocity defined by [-Offsetlimit,+Offsetlimit]. It calculates and activates a DAC offset that minimizes the lag error in the position control. Offset filter time float >=0 s Integrator time constant. Offset limit float >=0 The upper limit of the active range of the offset calibration as a relative proportion of the output magnitude. Position control: acceleration pre- control Ka float >=0 s Output velocity component = Ka · set acceleration.