omron — 4-4-5 Wiring the Inverter’s EtherCAT Communications Unit and Robot

4 Implementation Example of Dynamic Pick-and-place Equipment 4-4-3 Wiring the EtherCAT Digital I/O Terminal and Inverter’s EtherCAT Communications Unit Wire the EtherCAT Digital I/O Terminal and EtherCAT Communications Unit of the Inverter. 1 Connect the EtherCAT OUT port of the EtherCAT Digital I/O Terminal and the EtherCAT IN port on the EtherCAT Communications Unit with an Ethernet cable.

4-4 Installing and Wiring the System Communications connector (IN) Communications connector (OUT) 4 4-4-4 Setting the Node Address of Inverter’s EtherCAT Communica- tions Unit 4-4-3 Wiring the EtherCAT Digital I/O Terminal and Inverter’s EtherCAT Communications Unit This section describe the settings of the EtherCAT node address of the EtherCAT Communications Unit of the inverter. 1 Set the switches for the EtherCAT node address on the EtherCAT Communications Unit of the inverter. To set the node address to 2, set the x10 switch to 0 and the x1 switch to 2.

Node address setting (x1) Node address setting (x10) Precautions for Correct Use Set the EtherCAT node address of the inverter to be the same as the node address set in 3-3-2 Creating the EtherCAT Network Configuration on page 3-20. 4-4-5 Wiring the Inverter’s EtherCAT Communications Unit and Robot In this section, wire the EtherCAT communications unit of the inverter and the robot. 4-95 NJ-series Robot Integrated System Startup Guide (O049)