omron — 4-5-1 Communications Setup

4 Implementation Example of Dynamic Pick-and-place Equipment 4-5 Operation Check on the Actual Sys- tem 4-5 Operation Check on the Actual System This section describes the procedures for checking operation and adjusting the system on the actual system. Check operation with the simulation function before you check operation on the actual system. Precautions for Correct Use When you operate the robot in MANUAL mode with the T20 pendant, you must plug the iCS Commissioning Jumper into the XBELTIO connector and change the setting for the Teach Re- strict. Refer to iX4 650 H/HS and 800 H/HS Robot with EtherCAT User’s Guide (Cat. No. I656) for details.

4-5-1 Communications Setup 4 4-5-1 Communications Setup Set up Sysmac Studio installed on your PC to communicate with the Robot Integrated CPU Unit. In this section, IP address of the EtherNet/IP port on the Robot Integrated CPU Unit to connect to the computer is set to 192.168.250.1. Also set the IP address of the camera to the IPC Application Controller in advance. For procedure to set the IP address of the camera to the IPC Application Controller, refer to Appendix A of the Automation Control Environment (ACE) Version 4 User’s Manual (Cat. No. I633) . 1 Boot up the Sysmac Studio. 2 Clear the Open in Emulation Mode check box at the bottom left of the start page.

3 Click the Open Project tab. 4-103 NJ-series Robot Integrated System Startup Guide (O049) Setting Up Sysmac Studio to Communicate with the Robot Integrat- ed CPU Unit