omron — 1.2.3 Hide or show decimals

OMRON Quick Start Instruction E5CC 1.2.2 Setting the sensor type To set the sensor type, you need to change the parameter in-t (input- type) . Do this as follows: 1. Press the 1 st button (level button) at least 3 seconds until in-t is displayed. 2. The set value is indicated green and will default to 5. 3. If you are using a different sensor type, please enter the number next to the type used. Section 1.2.1 4. You can change the value with the up / down button. 5. After changing the value, press the level button for 3 seconds again. If s-err is displayed on the controller, then the sensor has not been connected properly, the incorrect type has been selected, or the sensor has a malfunction.

Example: If you are using a Pt100, then you will see in the table on page 9 that you can select either the value 0.1 or 2. The difference between these settings is the range and the decimal point (see also Section 1.2.3. ) 1.2.3 Hide or show decimals To show or hide decimals, first change the sensor type, see Figure 6 in Section 1.2.1 . Next to Pt100 in the table is setting 0.1 or 2. If we indicate the number 0 , then the range is -200 to 850 degrees WITHOUT decimals; number 1 ranges from -199.9 to 500.0, WITH decimals. 10