Delta OPC — 4.1.1 Conversion

Chapter 4 Advanced Functions of Delta OPC Figure 4-2 Setting a conversion  Users can type the name of the conversion created. They can type 50 characters at most.  Users can select a conversion type. If the No (make float) option button is selected, no conversion will be carried out. If the Linear option button is selected, a register value in the range of the maximum register value set to the minimum register value set will correspond to a value in the range of the maximum engineering value set to the minimum engineering value set. If the Square root option button is selected, the square root of a value will be calculated.

In the Conversion parameters section, the users can set a minimum register value in the Low IR (instrument range) box, a maximum register value in the High IR (instrument range) box, a minimum engineering value in the Low EU (engineering unit) box, and a maximum engineering value in the High EU (engineering unit) box.  If the None option button in the Clamping section is selected, there will be no maximum engineering value and no minimum engineering value. If the Clamp on EU option button in the Clamping section is selected, the value in the Low EU box will be a minimum engineering value, and the value in the High EU box will be a maximum engineering value.

If the As specified option button is selected, the value in the Low clamp box will be a minimum engineering value, and the value in the High clamp box will be a maximum engineering value. After the users complete the setting of a conversion, they have to click Apply to write the setting into the config file created. If the users click Reset , the previous setting saved will be restored. If the users click Add New , a new conversion will be created. After the users complete the setting of conversions, they can click a data item which needs to be converted in the project management area.

After the users select the Use conversion checkbox, they can select a conversion which has been created in the Name drop-down list box, as shown in figure 4-3. Figure 4-3 Using a conversion 4-3