Delta OPC — 4.1.3 Alarm

Delta OPC User Manual  Limit Alarm Definition After a new limit alarm is created, the window appearing will be as shown in figure 4-11. The items which need to be set are described below. Figure 4-11 Setting an alarm  Users can type the name of the alarm created. They can type 50 characters at most. The value in the Update rate box indicates the frequency with which the status of the alarm created is updated. The users can set a value in the Deadband box. In order to prevent an alarm from being triggered continually by the oscillations of a value around a limit value, the alarm is triggered only once when the oscillations of a value stay within a deadband.

 Users can set limit values in the Limit alarm definition section.  Limit : If the Limit checkbox for a limit value is selected, the alarm created is triggered when the value in a register reaches the limit value. Users can set four limit values. If the Return to normal checkbox is selected, a message is displayed when the value in a register returns to normal.  Value : Users can set limit values.  Message Body : Message displayed in a client when the value in a register reaches a limit value  Severity : Degree of severity displayed in a client when the value in a register reaches a limit value  Req. Ack. :

If the alarm created is triggered, it will not be canceled until an acknowledgement is given. After the users complete the setting of an alarm, they have to click Apply to write the setting into the config file created. If the users click Reset , the previous setting saved will be restored. If the users click Add New , a new alarm will be created. 4-8