Delta OPC — 4.1.4 Testing the Connection of an OPC Client

Delta OPC User Manual Figure 4-13 Starting an alarm 4.1.4 Testing the Connection of an OPC Client If users want to connect an OPC client to Delta OPC, they have to use the OPC client to search for the OPC servers which exist in the computer used, and select a connection. The creation of a connection between iFIX and a Delta OPC server is shown in figure 4-14. (Note: Please refer to related manuals for more information about the operation and usage of iFIX.) In figure 4-14, iFIX finds the OPC servers which have been installed on the computer used. If users want to connect iFIX to a Delta serial OPC server, they have to select Delta.AHModbusSerialDA or Delta.AHModbusSerialDA.1.

If the users want to connect iFIX to a Delta Ethernet OPC server, they have to select Delta.AHModbusEthernetDA or Delta.AHModbusEthernetDA.1. Figure 4-14 Selecting a Delta OPC server which is running The users have to select the registers which they want to monitor. A shown in figure 4-15, the hierarchical structure created in a Delta OPC configurator is shown in the Path section, and the data items created in the Delta OPC configurator are shown in the Items section. In figure 4-15, Port_1.PLC_1.TAG1 indicates the port, device, and data item created in a Delta OPC configurator. After the users select data items, they can add the data items to the list which iFIX will monitor. 4-10