Orion-Tr Smart DC-DC Charger Non-Isolated 5. 4 → 5: If V start(delay) IN start , charging is enabled after t start delay (configurable). 5.2. Engine shutdown detection setup with VictronConnect Open VictronConnect and press the cog symbol to enter the settings. Figure 9: Engine shutdown detection setup menu The following settings can be changed with VictronConnect: The default values displayed are for 12V input models. These values are scaled based on the model's input voltage. For example, for 24V input models, the default values in the manual should be multiplied by 2, and for 48V models, they should be multiplied by 4. Engine shutdown detection enabled :
The engine shutdown detection is always enabled by default when the charger mode is selected. When it is disabled by the user or when power supply mode is selected, the engine is considered to be running, so no shutdown detection will take place. Leave the engine shutdown detection enabled when an external engine running signal is connected: the signal only forces charging on, and disabling the detection makes the charger charge continuously regardless of the signal. See the Using an external engine running signal [13] section. Alternator type: The alternator type can be selected between “Smart Alternator”, “Regular Alternator”, and “User defined”.
When the “Smart Alternator” option is selected, the default values for the smart alternator are/will be applied to the engine shutdown detection settings. The same will happen when the “Regular Alternator” option is selected. When any settings differ from the default values of the last two options, the “User defined” option will be selected. Default: “Smart Alternator”. Start voltage (V start ): At this level, charging starts immediately. Delayed start voltage (V start(delay) ): Smart alternators can generate a lower voltage when the engine is running; therefore, a lower start level is necessary for these systems.
To ensure that the starter battery is recharged after starting the engine, charging of the auxiliary battery is delayed during this condition. The energy used during starting must be replenished to ensure that the starter battery remains properly charged. Delayed start voltage delay (t start delay ): Recharge time for the starter battery during start level (delayed). Example: If the starter draws 150A for 5sec to start the engine, about ~0.2Ah is drawn from the starter battery. If, during engine idling, the alternator can only generate 20A, it takes 150A/20A x 5sec =37.5sec to recharge the starter battery. Shutdown voltage (V shutdown ): This level corresponds with the engine being off.
This keeps the starter battery fully charged and provides a hysteresis with respect to the start level. The hysteresis must be large enough to prevent V IN to drop to V shutdown , which would result in charge current reduction. Action will be taken after tshutdown runs out (1 minute); this allows charging during temporary low voltage conditions. The default values depend on the selected alternator type. Values are given as 12V / 24V / 48V input model.
Setting Smart Alternator Regular Alternator Start voltage (V start ) 14V / 28V / 56V 14V / 28V / 56V Delayed start voltage (V start(delay) ) 13.3V / 26.6V / 53.2V 13.8V / 27.6V / 55.2V Delayed start voltage delay (t start delay ) 120s 120s Shutdown voltage (V shutdown ) 13.1V / 26.2V / 52.4V 13.5V / 27V / 54V Range for engine start/shutdown levels: Page 11 Automatic engine shutdown detection