Delta Electronics — 2.8.2 Network Module Profiles

Chapter 2 Specifications and System Configuratio n 2_ 2-70 Number Name Description RTU mode:  NS LED OFF: no power or duplicate ID check has not been completed. Green light blinking every 0.5 seconds: the connection to the DeviceNet network failed. Green light ON: online; the connection to the DeviceNet network is normal. Red light blinking every 0.5 seconds: I/O connection timeout between AS01DNET (RTU) and DeviceNet master Red light ON: Network trouble, duplicate node ID, no network power or Bus-OFF.  MS LED OFF: no power Green light blinking every 0.5 seconds: - AS01DNET (RTU) is waiting for the I/O data from DeviceNet master.

- No I/O data transmission between AS01DNET(RTU) and DeviceNet master - The PLC connected to DeviceNet master is in STOP state. Green light ON: normal transmission of I/O data between AS01DNET (RTU) and DeviceNet master Red light blinking every 0.5 seconds: no network power supply; configuration error; module alarms. Red light ON: hardware error 3 Address switch Setting up the address Setting up the funcitons, including the work mode and baud rate 4 Function switch of DeviceNet network DeviceNet communication Connects the modules via DeviceNet communication. 5 port Use AS01DNET-A connector for wiring. Master/Slave mode:

the port does not need an external Mode switch 24VDC power supply connected 6 (RTU/DNET; RTU mode: the power input port of the network module is Master/Slave) required to connect an external 24VDC power supply only. You can connect 7 Left-side extension port Connects the modules 8 Label Nameplate 9 Right-side extension port Connects the modules Input for supplying power 10 Power supply for the remote module to remote modules