Delta Electronics — 2.9.1 General Specifications

AS Series Operation Manual 2.9 Load Cell Module Specifications 2.9.1 General Specifications  AS02LC-A _2 2-73 Load cell module Voltage output Rated supply voltage/Power 24 VDC (-15 to +20%) / 5W consumption Minimum/maximum voltage 18~31.2VDC Maximum current consumption 150 mA Input signal range ±40mVDC Sensibility +5 VDC +/-10% ADC resolution 24 bits Highest precision 0.04% Applicable sensor type Four-wire or six-wire load cell Expanding a temperature ≤ ± 50 ppm/K v.

E coefficient Reducing a temperature ≤ ± 0.4 μV/K coefficient to zero Linearity error ≤ 0.02% Response time 2.5, 10, 16, 20, 50, 60, 100, 200, and 400ms Eigenvalue applicable to a load 0–1, 0–2, 0–4, 0–6, 0–20, 0–40 and 0–80 mV/V cell Maximum distance for 100 meters connecting a load cell Maximum output current 5 VDC * 160 mA Allowable load 40–4,010 Ω Common-mode rejection ratio ≥100 dB (CMRR @50/60 Hz) Dynamic range K1–K5 Averaging weights K1–K100 Between a digital circuit and the ground: 500 VAC Between an analog circuit and the ground: 500 VAC Between an analog circuit and a digital circuit: 500 VAC Isolation Weight 140 g