Chapter 4 Installing Hardware 4.2 Wiring 4.2.1 Wiring a Power Supply Module A power supply module supplies direct current to a CPU module and I/O modules.  Connecting an AC power cable Control Box 100~240V 4_  The alternating-current input voltage is either 100 VAC or 240 VAC. Connect the power supply to the and 24G, the PLC will be damaged. terminals L and N. If the 110 VAC or the 220 VAC power supply is connected to the input terminals +24V  If power is interrupted for less than 10 milliseconds, the PLC keeps running without being affected. If a power interruption lasts for longer, or if the voltage of the power supply decreases, the PLC stops running, and there is no output.

When the power supply returns to normal, the PLC resumes. Notice that there are latched auxiliary relays and registers in the PLC when you write the program.  Use single-wire cables or two-wire cables in a diameter of 22 AWG~18 AWG and with less than 2 mm pin-typed terminals. Only use copper conducting wires with a temperature of 60/75°C. 22-18AWG 11-12mm 4.2.2 Wiring I/O Modules The I/O modules include digital input/output, analog input/output, and network modules. Follow the directions for the wiring of I/O modules in Chapter 5 of the AS Series Hardware Manual. 4-5 PS02A +24V 24G L N LG AS Series 06XA 24V 0V